Free tools · BS 5839-1:2025

Fire alarm calculators

Standby battery capacity and false alarm rate, worked out the way BS 5839-1:2025 says, with every result tied to its clause and the working shown so you can check it. Free, no sign-up, nothing you type leaves your browser.

Calculator 01 · Clause 24.3 & Annex E

Standby battery calculator

Minimum battery capacity (Cmin) for a valve-regulated lead acid standby battery, with the standby period set by the system category and how the building is used.

1 · System category
2 · The building
h
h
3 · Currents

Currents per item from the manufacturers' data sheets, in milliamps. Alarm current is what each item draws with the system in alarm (3.40 counts every sounder and beacon running, plus alarm signals from the detectors and call points).

ItemQtyStandby mA eachAlarm mA each
Totals0 mA0 mA
4 · Alarm period and derating
h
Calculator 02 · Clause 31 & Annex F

False alarm rate calculator

The rate per 100 detectors per annum, and every trigger in clause 31 for a review, a preliminary investigation or an in-depth investigation. Work it out per system, not across a whole estate.

1 · The system
2 · The previous 12 months
3 · Since the last service visit

FireCompliance Pro does both of these on every service visit. The engineer's form works out Cmin from the currents they measure and puts it on the certificate, and the false alarm log is kept per system with the clause 31 rate in front of the engineer and your client.

Start your free trial

How these work, and their limits

Standby period (24.3.5). Category M and L systems need 24 hours, or 6 hours where an automatically started generator serves the whole system. Category P systems need 24 hours more than the longest time the building is likely to be empty, up to 72 hours in total, or 24 hours if a power supply fault would be noticed within 6 hours or is signalled to an alarm receiving centre that alerts a keyholder straight away. The generator relaxation never applies to P. A combined system (4.5) has to meet both, so the P period decides. After the standby period, 30 minutes of alarm is added.

Capacity (Annex E). Cmin = 1.25 (T1I1 + D I2T2). D is 1 when Cmin/20 is at least I2; otherwise it is the battery maker's figure or 1.75. The check uses Cmin worked out with D = 1. Where the result isn't a size you can buy, go up to the next size (E.1.3); the sizes shown are common ones, so check your supplier's range and what the panel's charger and battery space will take. On a 24 V panel the two 12 V batteries are in series, so each battery is the capacity shown, not half of it.

  • Annex E covers valve-regulated lead acid batteries only. For any other battery type the standard sends you to the manufacturer (E.2).
  • The charger has to bring the battery back to this capacity within 24 hours from its final voltage (24.3.4).
  • Extra indicating equipment that isn't the default means of control can have a shorter standby period of 4 hours in some cases (24.3.6); this calculator doesn't cover that.

False alarms (clause 31, Annex F). The rate is 100 times the false alarms in the previous 12 months divided by the number of automatic fire detectors. Following the standard's own worked examples, an aspirating detector or a beam counts as one detector, call points are not counted, and false alarms from call points are left out of the rate. Every false alarm should get a review. A preliminary investigation is needed if the rate is over 4, there have been more than 10 since the last visit, more than one (not counting good intent) has come from one device since the last visit, there is a persistent cause, or there have been more than 2 unwanted fire alarm signals in 12 months. With more than 40 detectors, an in-depth investigation is advised if the rate is over 5 or one device has caused more than 2 in 12 months; with 40 or fewer, if there have been more than 2 false alarms in 12 months. A Category M system has no detectors, so it has no rate.

These tools follow BS 5839-1:2025 clause 24.3, Annex E, clause 31 and Annex F, and are checked against the standard's worked examples. They are an aid for competent people, not a replacement for the standard, the manufacturer's data or your own judgement. Spotted something that doesn't match your reading of the standard? Tell us at hello@firecompliancepro.com and we'll fix it.